TEOS +100

1 - 3 kVA

High frequency on-line double conversion technology, Active power factor correction (APFC), input power factor up to 0.99, Output power factor 0.9, Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz), 50/60Hz frequency conversion

Show More

Areas of Usage

General Features

TEOS +100
  • High frequency on-line double conversion technology
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)
  • 50/60Hz frequency conversion
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restored in 3 h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Settable delayed start when power is restored
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode
  • Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
  • Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function, and 12 A charger (2/3 kVA only)
TECHNICIAL SPECIFICATIONS
Capacity1 kVA/900 W
INPUT
Voltage208 / 220 / 230 / 240 Vac
Voltage range110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Frequency40 ~ 70 Hz (auto-sensing)
Power factor≥ 0.99
Bypass voltage range− 25% ~ +15% (settable)
THDI≤ %6
OUTPUT
Voltage208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation± %1
Frequency45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
WaveformSinusoidal
Power factor0.9
THD≤ 2% (linear load), ≤ 5% (non-linear load)
Output current crest factor3:1
Overload105% ~ 125% for 1 min, 125% ~ 150% for 30 s, > 150% for 300 ms
BATTERIES
DC Voltage24V (S) - 36V (S) - 36V (H)
Internal battery pack2x9Ah - 3x7Ah - /
Charging current (max.)1A - 6A
Battery charge timeStandard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
ENVIRONMENT
Efficiency≥ %90 (Mains mode)
≥ %85 (Battery mode)
≥ %95 (ECO mode)
Transfer timeMains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)
ProtectionShort-circuit, overload, overtemperature, battery discharge protection and fan testing protection
CommunicationRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
DisplayLCD + LED
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
OTHER FEATURES
Operating temperature0°C ~ 40°C
Storage temperature− 25°C ~ 55°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000 m, derating 1% for each additional 100 m
Protection classIP 20
Noise level≤ 50 dB
Dimension (mm) HxWxD144x336x214
144x414x 214
144x336x214
Packed dimensions (mm) WxDxH232x417x 318
230x492x320
232x417x318
Weight (kg)9.5
13
6
Gross weight (kg)10.5
14.2
7
TECHNICIAL SPECIFICATIONS
Capacity2 kVA/1800 W
INPUT
Voltage208 / 220 / 230 / 240 Vac
Voltage range110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Frequency40 ~ 70 Hz (auto-sensing)
Power factor≥ 0.99
Bypass voltage range− 25% ~ +15% (settable)
THDI≤ %6
OUTPUT
Voltage208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation± %1
Frequency45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
WaveformSinusoidal
Power factor0.9
THD≤ 2% (linear load), ≤ 5% (non-linear load)
Output current crest factor3:1
Overload105% ~ 125% for 1 min, 125% ~ 150% for 30 s, > 150% for 300 ms
BATTERIES
DC Voltage48V (S) - 72V (S) - 72V (H)
Internal battery pack4x9Ah - 6x7Ah - /
Charging current (max.)1A - 6A
Battery charge timeStandard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
ENVIRONMENT
Efficiency≥ 91% (Mains mode)
≥ 86% (Battery mode)
≥ 96% (ECO mode)
Transfer timeMains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)
ProtectionShort-circuit, overload, overtemperature, battery discharge protection and fan testing protection
CommunicationRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
DisplayLCD + LED
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
OTHER FEATURES
Operating temperature0°C ~ 40°C
Storage temperature− 25°C ~ 55°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000 m, derating 1% for each additional 100 m
Protection classIP 20
Noise level≤ 50 dB
Dimension (mm) HxWxD191x418x335
Packed dimensions (mm) WxDxH318x533x471
Weight (kg)18
25.7
10.5
Gross weight (kg)19.5
27.4
12
TECHNICIAL SPECIFICATIONS
Capacity3 kVA/2700 W
INPUT
Voltage208 / 220 / 230 / 240 Vac
Voltage range110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)
Frequency40 ~ 70 Hz (auto-sensing)
Power factor≥ 0.99
Bypass voltage range− 25% ~ +15% (settable)
THDI≤ %6
OUTPUT
Voltage208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation± %1
Frequency45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode)
WaveformSinusoidal
Power factor0.9
THD≤ 2% (linear load), ≤ 5% (non-linear load)
Output current crest factor3:1
Overload105% ~ 125% for 1 min, 125% ~ 150% for 30 s, > 150% for 300 ms
BATTERIES
DC Voltage72V (S) - 96V (S) - 96V (H)
Internal battery pack6x9Ah - 8x7Ah - /
Charging current (max.)1A - 6A
Battery charge timeStandard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
ENVIRONMENT
Efficiency≥ 92% (Mains mode)
≥ 87% (Battery mode)
≥ 97% (ECO mode)
Transfer timeMains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical)
ProtectionShort-circuit, overload, overtemperature, battery discharge protection and fan testing protection
CommunicationRS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
DisplayLCD + LED
StandardsEN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
OTHER FEATURES
Operating temperature0°C ~ 40°C
Storage temperature− 25°C ~ 55°C (without batteries)
Relative humidity0 ~ 95% (non-condensing)
Altitude≤ 1000 m, derating 1% for each additional 100 m
Protection classIP 20
Noise level≤ 50 dB
Dimension (mm) HxWxD191x418x335
191x464x335
191x418x335
Packed dimensions (mm) WxDxH318x533x471
320x573x472
318x533x471
Weight (kg)27.2
32
11
Gross weight (kg)29
34
12.5

NameFile Size
1)TEOS+100 - ( 1 - 3 kVA )-

NameFile Size
1)TEOS+100 - (1-3 kVA)-