DS POWER H

300 - 400 kVA

The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance.

Show More

Areas of Usage

General Features

DS POWER H

3 LEVEL TECHNOLOGY

IGBT RECTIFIER
DSP CONTROL

The new DS Power range UPS uses the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. With the DS Power range, efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.

  • Transformerless UPS topology
  • 3 Level topology
  • High input power factor
  • High efficiency up to 95%
  • Cold start function
  • Static and maintenance by-pass switch
  • Output short circuit and overload protection
  • External REPO switch input
  • 512 events memory (512 events 45000 alarms)
  • Clock and calender (battery supported)
  • Automatic battery test,remaining battery time indicator
  • Temperature compansated charge system (optional)
  • 2 RS232 serial ports and 12 dry contact outputs
  • 3 DSP controlled modular structure
  • Optional SNMP and MODBUS adaptors
  • Optional graphical panel
  • Optional usb flash memory
  • Full digital structure
  • Small footprint
  • Ecomode operation (optional)
  • Fewer electronic components
  • Output current limiting
  • Advanced diagnostics for the input
  • Selectable input/output voltage/frequency/range
  • Split by-pass input (second input)
  • Output DC leakage protection
  • Separate DSP for inverter control
  • Separate DSP for the PFC
  • 3 level battery protection
  • High charge current capacity
  • Charge/discharge current indicator
  • Advanced remote control
  • Manufactured according to EC Directive; EN62040
  • 2 years warranty
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)300
INPUT
Voltage380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency50Hz / 60Hz, ± %5
Power factor (at100% load)≥ 0.99
THDI (*)≤ %3
By-Pass Voltage380/400 VAC 3 Phase + N, ± 10%
ProtectionFuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW)270
Power factor0,9 (0,8 and 1 optional)
Voltage380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency50Hz / 60Hz
Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load)up to 95%
Output current crest factor3:1
Overload Protection100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD≤ 2% (at 100% linear load)
BATTERIES
TypeVRLA AGM / GEL / NiCd
Battery Number2x30 (±30): 60 pieces
Float charging voltage2x405 VDC
Float / End of dischg voltage2x300 VDC
Battery HousingExternal
Battery ambient temp25ºC
Protections3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic TestingStandard every 72 hours (adjustable)
GENEL
StandardsEN62040-1, EN62040-2, EN62040-3
User Interface4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORSP-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
AdvancedSelf diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
InputsEPO input, Interactive battery panel input, Genset input
Genset KitStandard (programmable)
SoſtwareStandard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm LoggingStandard:with time & date 512 events
ProtectionsPower module over-temperature, Overcurrent, Temperature high alarm
Temperature Range0ºC - 40ºC
Protection classIP20
Relative humidity90% max. (non-condensing)
Altitude< 1000m above sea level
Noise level< 68 dBA
Weight (kg)635
Dimension (mm) HxWxD1250x775x1900
OPTIONS
Input / Output voltagePlease ask
TransformerGalvanic isolation transformer at the input & output (internal)
SoſtwareT-Mon Admin Multi UPS monitoring 10-50-100-200 kullanıcı , T-Mon Server 50-100-200 kullanıc
Comm. adaptorsSNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel OperationUp to 8 units
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)400
INPUT
Voltage380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load)
Frequency50Hz / 60Hz, ± %5
Power factor (at100% load)≥ 0.99
THDI (*)≤ %3
By-Pass Voltage380/400 VAC 3 Phase + N, ± 10%
ProtectionFuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW)360
Power factor0,9 (0,8 and 1 optional)
Voltage380/400 VAC 3P + N, ± 1% (415 VAC optional )
Frequency50Hz / 60Hz
Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load)up to 95%
Output current crest factor3:1
Overload Protection100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD≤ 2% (at 100% linear load)
BATTERIES
TypeVRLA AGM / GEL / NiCd
Battery Number2x30 (±30): 60 pieces
Float charging voltage2x405 VDC
Float / End of dischg voltage2x300 VDC
Battery HousingExternal
Battery ambient temp25ºC
Protections3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic TestingStandard every 72 hours (adjustable)
GENEL
StandardsEN62040-1, EN62040-2, EN62040-3
User Interface4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
INDICATORSP-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
AdvancedSelf diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
InputsEPO input, Interactive battery panel input, Genset input
Genset KitStandard (programmable)
SoſtwareStandard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm LoggingStandard:with time & date 512 events
ProtectionsPower module over-temperature, Overcurrent, Temperature high alarm
Temperature Range0ºC - 40ºC
Protection classIP20
Relative humidity90% max. (non-condensing)
Altitude< 1000m above sea level
Noise level< 68 dBA
Weight (kg)680
Dimension (mm) HxWxD1250x775x1900
OPTIONS
Input / Output voltagePlease ask
TransformerGalvanic isolation transformer at the input & output (internal)
SoſtwareT-Mon Admin Multi UPS monitoring 10-50-100-200 kullanıcı , T-Mon Server 50-100-200 kullanıc
Comm. adaptorsSNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer
Parralel OperationUp to 8 units